Thermafiber pioneered the testing of curtain wall fire containment in 1971 and continues to raise the bar with new tests each year. Our newest innovation, the Impasse® curtain wall insulation system, overlaps components during installation to lock in the fire barrier, virtually eliminating the possibility of insulation materials becoming dislodged by fire’s turbulent forces. Proprietary hangers also make installation of the Impasse system simple, accurate and fast. Thermafiber’s Safing insulation and FireSpan® 90 and FireSpan® 40 curtain wall insulations are approved for use in perimeter fire containment assemblies listed by UL® and Intertek.


Optional Fields:
Search Results
Frame Type Frame Choice UL Test SS Manufacturer Hourly Rating Products Description CAD
Aluminium Box Frame Spandrel Height 0" to 3" CW-D-1014 STI 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall system with glass/aluminum/stone panels. The height is reduced on the spandrel and vision panel sill. No stiffener tee.
Aluminium Box Frame Spandrel Height 0" to 3" CW-D-1015 Hilti 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall system with glass/aluminum/stone panels. The height is reduced on the spandrel and vision panel sill. No stiffener tee.
Aluminium Box Frame Spandrel Height 0" to 3" CW-D-1016 Rectorseal 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall system with glass/aluminum/stone panels. The height is reduced on the spandrel and vision panel sill. No stiffener tee.
Aluminium Box Frame Spandrel Height 0" to 3" CW-D-1017 3M 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall system with glass/aluminum/stone panels. The height is reduced on the spandrel and vision panel sill. No stiffener tee.
Aluminium Box Frame Spandrel Height 6" and above CW-D-1013 STI 1
1.5
2
FireSpan
FireLedge
Impasse Hanger System
Safing
No Backer Bar System
Aluminum box frame curtain wall system with glass/aluminum/stone panels. No Backer Bar System sill height. Minimum 6" Transom height. Spandrel Panel height is 36" CW-D-1013
Aluminium Box Frame Spandrel Height 6" and above CW-D-2042 STI 1
1.5
2
FireSpan
Safing
Sprial Anchors
Aluminum box frame curtain wall system with glass/aluminum/stone spandrels. Reduced spandrel panel height and vision panel sill height. Minimum 6" Transom height. Spandrel Panel height is 36"
Aluminium Box Frame Spandrel Height 30" and above CW-D-2039 STI 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum box frame curtain wall with glass spandrels. Impasse system with minimum 33" transom height. Spandrel Panel is 69". CW-D-2039
Aluminium Box Frame Spandrel Height 30" and above CW-D-2046 Hilti 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum box framed curtain wall with glass/aluminum/stone panels. Impasse System with minimum 33" transom height. Spandrel panel height is 69".
Aluminium Box Frame Spandrel Height 30" and above CW-D-2047 Rectorseal 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum box frame curtain wall with glass spandrels. Impasse system with minimum 33" transom height. Spandrel Panel is 69".
Aluminium Box Frame Impasse Hangers CW-D-1014 STI 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall system with glass/aluminum/stone panels. The height is reduced on the spandrel and vision panel sill. No stiffener tee. CW-D-1014
Aluminium Box Frame Impasse Hangers CW-D-2039 STI 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall with glass spandrel. Minimum 33" transom height, Spandrel panel is 69"
Aluminium Box Frame Impasse Hangers CW-D-1015 Hilti 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall system with glass/aluminum/stone panels. The height is reduced on the spandrel and vision panel sill. No stiffener tee.
Aluminium Box Frame Impasse Hangers CW-D-2046 Hilti 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum box framed curtain wall with glass/aluminum/stone panels. Impasse System with minimum 33" transom height. Spandrel panel height is 69".
Aluminium Box Frame Impasse Hangers CW-D-1016 Rectorseal 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall system with glass/aluminum/stone panels. The height is reduced on the spandrel and vision panel sill. No stiffener tee.
Aluminium Box Frame Impasse Hangers CW-D-2051 Rectorseal 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall with glass spandrel. Minimum 33" transom height, Spandrel panel is 69"
Aluminium Box Frame Impasse Hangers CW-D-1017 3M 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum frame curtain wall system with glass/aluminum/stone panels. The height is reduced on the spandrel and vision panel sill. No stiffener tee.
Aluminium Box Frame Impasse Hangers CW-D-2055 3M 1
1.5
2
FireSpan
Impasse Hanger System
Safing
Aluminum box framed curtain wall with glass/aluminum/stone panels. Impasse System with minimum 33" transom height. Spandrel panel height is 69".
Aluminium Box Frame Exterior Installation CW-D-2056 STI 1
1.5
2
Firespan
Safing
Aluminum framed curtain wall with glass/aluminum/stone spandrels. Exterior Installation. I Shape Mullions. Minimum 6" Spandrel height. Spandrel height is 36". CW-D-2056
Aluminium Box Frame Traditional Impaling Pins CW-S-2003 STI 1
1.5
Firespan
Safing
Aluminum box framed curtain wall with glass spandresl. Steel perimeter angle around framed opening. Minimum transom height 24". Spandrel panel height is 60".
Aluminium Box Frame Traditional Impaling Pins CW-S-2003 STI 2 Firespan
Safing
Aluminum box framed curtain wall with glass spandrels. Steel perimeter angle around framed opening. Minimum transom height 34". Spandrel panel height is 69".
Aluminium Box Frame Steel BackPan (inboard) CW-S-0004 STI 1
1.5
2
Firespan
Safing
Steel backpan system. Aluminum framed curtain wall with glass/aluminum/stone spandrel panels. Transom minimum 6" above floor. Spandrel panel height is a minimum 36". CW-S-0004
Aluminium Box Frame Steel BackPan (outboard) CW-D-1004 STI 1
1.5
2
Firespan
Safing
Steel backpan system. Aluminum framed curtain wall with glass/aluminum/stone spandrel panels. Transom minimum 34" above floor. Spandrel panel height is a minimum 66". CW-D-1004
Aluminum "I" Mullion Frames 3" Firespan 90 CW-D-1008 STI 1
1.5
2
Firespan
Safing
Aluminum framed curtain wall with glass/aluminum/stone spandrels. Reduced spandrel panel hegiht and vision panel sill height. Transom minimum 6" above floor. Spandrel Panel height minimum 36".
Aluminum "I" Mullion Frames 4" FireSpan 40 CW-D-2057 STI 1
1.5
2
Firespan
Safing
I-Mullion curtain wall system with glass/aluminum/stone spandrels. Reduced spandrel panel height and vision panel sill height. Steel Hat Channels. Transom height minimum 6". Spandrel panel height minimum 36".
Aluminum "I" Mullion Frames Large Joint (10") CW-D-2057 STI 1
1.5
2
Firespan
Safing
I-Mullion curtain wall system with glass/aluminum/stone spandrels. Reduced spandrel panel height and vision panel sill height. Steel Hat Channels. Transom height minimum 6". Spandrel panel height minimum 36".
Steel Stud Frame Exterior Stud Wall CW-S-1002 STI 1
1.5
2
Firespan
Safing
Gypsum sheathed/steel stud wall. 3" Firespan 90 in stud cavity Various finishes: brck/metal/stucco. Window minimum 34" above floor and minimum 33" below floor. Spandrel panel width is 71.5" CW-S-1002
Steel Stud Frame Exterior Stud Wall CW-S-1010 STI 1
1.5
2
Firespan
Safing
Gypsum sheathed/steel stud wall. 4" FireSpan 40 used in stud cavity. Various finished: brick/metal/stucco. Window width 34" minimum above floor and minimum 33" below floor. Spandrel panel width is 71.5"
Steel Stud Frame Cantilever Wall CW-S-0001 STI 1
1.5
2
Firespan
Safing
Stud wall cantilver overedge with low sill height. Various exterior finishes: brick/metal/EIFS/GFRC.
Steel Stud Frame Window Sill Height Min 6" CW-S-1022 STI 1
1.5
2
Firespan
Safing
Gypsum sheathed/steel stud wall with low sill height. Various finshes: brick/metal/EIFS/stucco.
Steel Stud Frame Large Joint (10") CW-S-2066 STI 1
1.5
2
3
Safing I-Mullion curtain wall system with glass/aluminum/stone spandrels. Spandrel panel and vision panel sill height is reduced. 6" minimum window height. Minimum of 36" between windows (spandrel panel)
No Frame (with Concrete Panel) Uninsulated CW-D-2005 STI 1
1.5
2, 3
Safing Uninsulated concrete or tilt up panels (min 4" thick). Windows minimum 6" above floor. 36" minimum spandrel between windows CW-D-2005
No Frame (with Concrete Panel) Uninsulated CW-D-1018 Hilti 1
1.5
2, 3
Safing Uninsulated concrete or tilt up panels (min 4" thick). Windows minimum 6" above floor. 36" minimum spandrel between windows
No Frame (with Concrete Panel) Insulated CW-D-2006 STI 1
1.5
2
Safing Insulated concrete or tilt up panels with min 2" thick insulation. Minimum of 36" between windows (spandrel panel) CW-D-2006
No Frame (with Concrete Panel) GFRC uninsulated CW-S-2066 STI 1
1.5
2, 3
Safing I-Mullion curtain wall system with glass/aluminum/stone spandrels. Spandrel panel and vision panel sill height is reduced. 6" minimum window height. Minimum of 36" between windows (spandrel panel)